The ID jumper must be set to the correct values to identify the components on the 'PACE-Bus' (RS485). The ID must be unique on one 'PACE-Bus' (RS485).
The ID jumper 7 and 8 are used to set the RS485 address.
7 | 8 | ID |
---|---|---|
0 | 0 | 10 |
0 | 1 | 11 |
1 | 0 | 12 |
1 | 1 | 13 |
- 0 = OFF; no jumper is set
- 1 = ON; jumper is set
ID jumper 1 to 3 settings:
ID jumper | Function |
---|---|
1 | Analog control inputs are used as supervised inputs |
2 | Analog control inputs are used to supervise relay outputs |
3 | Logic control inputs 1 to 8 are used as relay controls |
The ID jumper 4 to 6 are reserved for future application and should stay in the OFF position.