The ID switch must be set to the correct values to identify the components on the serial 'PACE-Bus' (RS485). The ID must be unique on one 'PACE-Bus' (RS485).
1 | 2 | 3 | 4 | 5 | 6 | 7 | ID | Description |
---|---|---|---|---|---|---|---|---|
0 | 0 | 0 | 0 | 0 | X | X | - | Not allowed |
1 | 0 | 0 | 0 | 0 | X | X | - | Not allowed |
0 | 1 | 0 | 0 | 0 | 0 | 0 | 2 | Master component |
1 | 1 | 0 | 0 | 0 | 0 | 0 | 3 | Master component |
0 | 0 | 1 | 0 | 0 | 0 | 0 | 4 | Master component |
1 | 0 | 1 | 0 | 0 | 0 | 0 | 5 | Master component |
0 | 1 | 1 | 0 | 0 | 0 | 0 | 6 | Master component |
1 | 1 | 1 | 0 | 0 | 0 | 0 | 7 | Master component |
0 | 0 | 0 | 1 | 0 | 0 | 0 | 8 | Master component |
1 | 0 | 0 | 1 | 0 | 0 | 0 | 9 | Master component |
0 | 1 | 0 | 1 | 0 | 0 | 0 | 10 | Master component |
1 | 1 | 0 | 1 | 0 | 0 | 0 | 11 | Master component |
0 | 0 | 1 | 1 | 0 | 0 | 0 | 12 | Master component |
1 | 0 | 1 | 1 | 0 | 0 | 0 | 13 | Master component |
0 | 1 | 1 | 1 | 0 | 0 | 0 | 14 | Master component |
1 | 1 | 1 | 1 | 0 | 0 | 0 | 15 | Master component |
0 | 0 | 0 | 0 | 1 | 0 | 0 | 16 | Master component |
1 | 0 | 0 | 0 | 1 | 0 | 0 | 17 | Master component |
X | X | X | X | 1 | 0 | 0 | - | Higher numbers are not allowed |
X | X | X | X | X | 1 | 0 | 1 | Not allowed, first extension component |
X | X | X | X | X | 0 | 1 | 2 | Not allowed, second extension component |
X | X | X | X | X | 1 | 1 | 3 | Not allowed, third extension component |
- 0 = OFF; 1 = ON
- X = undefined; can be OFF or ON
- The master component is defined with the switches 6 and 7 = 0.
- The valid address range is from 2 to 17.