Follow the steps below to change the ID settings:
- Disconnect the 24 V power supply from the PTO2001-A1.
- Press and hold the keypads 00 and 11 on the PTO2001-A1.
- Connect the 24 V power supply to PTO2001-A1.
- The PTO2001-A1 switches to the configuration mode with a LED lamp test: red/green/yellow LEDs are activated.
- Afterwards the ID is indicated with a green blinking LED.
- Push the corresponding keypad button to set the new ID (refer to the table below).
- Push button 35 to confirm and write the new ID to flash.
- Perform a power reset with a disconnecting and re-connecting of the 24 V power supply to switch to the normal mode.
Push keypad | 00 | 01 | 02 | 03 |
To set ID | ID1 | ID2 | ID3 | ID4 |
To reconfirm the correct ID settings, please check them. See Check the ID settings.