Follow the steps below to check the ID settings:
- Disconnect the 24 V power supply from the PTO2001-A1.
- Press and hold the keypads 00 and 11 on the PTO2001-A1.
- Connect the 24 V power supply to PTO2001-A1.
- The PTO2001-A1 switches to the configuration mode with a LED lamp test: red/green/yellow LEDs are activated.
- Afterwards the ID is indicated with a green blinking LED (refer to the table below).
- Perform a power reset with a disconnecting and re-connecting of the 24 V power supply to switch to the normal mode.
Green blinking keypad | 00 | 01 | 02 | 03 |
ID of PTO2001-A1 | ID1 | ID2 | ID3 | ID4 |