The PT2006-A1 provides a configuration menu to change the following:
- The brightness of the display
- The RS485 ID
The RS485 ID must be set to the correct value to identify the component on the 'PACE-Bus' (RS485).
The ID must be unique on one 'PACE-Bus' (RS485).
Perform the following steps to change the RS485 ID and the brightness:
- Press button 1 and 6 at the same time to enter the configuration menu.
- The RS485 ID is displayed.
- Press button 6 (cfg) to change the configuration.
- The values for the RS485 ID and the brightness are displayed.
Button 2 - change between the RS485 ID and the brightness configuration
Button 1 - change the values, count down
Button 3 - change the values, count up
Button 4 - quit - leave configuration menu without saving the changes
Button 6 - save - save changes and leave the configuration menu