The ID jumper must be set to the correct values to identify the components on the 'PACE-Bus' (RS485). The ID must be unique on one 'PACE-Bus' (RS485).

The ID jumper 7 and 8 are used to set the RS485 address.

PCIO2001-A1 set the RS485 address with ID jumper

7

8

ID

0

0

10

0

1

11

1

0

12

1

1

13

  • 0 = OFF; no jumper is set
  • 1 = ON; jumper is set

ID jumper 1 to 3 settings:

PCIO2001-A1 function settings with ID jumper

ID jumper

Function

1

Analog control inputs are used as supervised inputs

2

Analog control inputs are used to supervise relay outputs

3

Logic control inputs 1 to 8 are used as relay controls

The ID jumper 4 to 6 are reserved for future application and should stay in the OFF position.