The 'EOL3 (active)' PCA2004-A1 provides an ID switch at the outside of its housing to set the EOL3 ID.
The EOL3 ID must be set to the correct value to identify the component on the 100 V speaker line.
The EOL3 ID must be unique on one digital audio matrix with an allowed EOL3 ID range of 1 to 63. The EOL3 ID at one speaker line must be set in sequence without gaps, e.g.: 3, 4, 5, 6.
In systems with multiple digital audio matrices, an EOL3 ID can be assigned multiple times.
Definition |
| Example 26 | ||
|---|---|---|---|---|
ID switch | Value | ID | Value | |
1 | 1 |
| OFF | - |
2 | 2 | ON | 2 | |
3 | 4 | OFF | - | |
4 | 8 | ON | 8 | |
5 | 16 | ON | 16 | |
6 | 32 | OFF | - | |
7 | OFF | OFF | - | |
8 | OFF | OFF | - | |
- | - | Sum | 26 | |