The door hinge of the 'Voice alarm panel Compact 400' PC1001-A3 and the 'Voice alarm panel Compact 1000' PC1002-A3 cabinets can be changed with the following steps:
- Unscrew the two door locks and remove both screws from them.
- Unscrew the covers on both door locks.
- Remove the upper and lower door protections.
- Unscrew the earth connection on the door.
- Unscrew the earth connection in the cabinet.
- Pull the upper hinge lever and move the door out of position, then take the door out of the cabinet. Please ensure that the washer of the lower hinge is not lost.
- Remove the upper and lower door holders.
- A: take off the washer
- B: unscrew the hinge stud
- Take the spring out of the hinge.
- Mount the door holders on the other side of the door:
- Insert the spring from outside
- Insert the lever
- Screw the hinge stud to the lever
- Place the door with the lower stud in the new position. Don't forget the washer.
- Pull the upper door lever and move the door into the new position, then release the lever and make sure that the door is properly inserted and secure. Don't forget the washer.
- Mount the earth connection in the new position in the cabinet.
- Mount the earth connection on the door.
- Mount the door protection in the new position.
- Mount the door locks and the door lock covers in the correct position.