Overview

Online system Desigo V6.3 with PXC4 and PXC5

  • Full BACnet communication between the Desigo CC management platform and the Desigo V6.3 system.
  • Full BACnet communication between the Desigo CC management platform and the Desigo PXC4 and PXC5 system.
  • BACnet communication between Desigo V6.3 and Desigo PXC4 and PXC5: Via COV's.

For system limits of Desigo V6.3, see Compatibility.

For system limits of Desigo PXC4 and PXC5, see PXC4 & PXC5 Planning Overview (A6V11973797).

Prerequisites for extending Desigo V6.3 (XWP project) with PXC4 and PXC5

  • Upgrade the management platform Desigo CC to V5.0.
  • Make sure all PXC00...200..D primary controllers and room automation products adhere to the Desigo V6.3 compatibility.
  • You are using Desigo Xworks Plus (XWP) V6.3.
  • You are using ABT Site V4.3.

Engineering of Desigo V6.3 projects with PXC4 and PXC5

Network topology

Structure the network topology as follows:

For more information, see Application Guide for BACnet Networks in Building Automation (A6V11159798).

Engineering and commissioning of Desigo PXC4 and PXC5

Engineer and commission the Desigo PXC4 and PXC5 subsystem with ABT site V4.3 and export/import it into the Desigo CC management platform.

For more information on the system compatibility of the Desigo CC management platform, see Desigo CC System Description (A6V10415500).

Engineering and commissioning of Desigo V6.3

Engineer enhancements and adaptations in Desigo V6.3 with XWP V6.3 (ABT Site) and export/import it into the Desigo CC management platform.

For more information on the system compatibility of the Desigo CC management platform, see Desigo CC System Description (A6V10415500).

Data exchange between Desigo V6.3 and Desigo PXC4 and PXC5 on automation level

Similar to the integration of third-party systems via BACnet references into the Desigo V6.3 system engineered via XWP V6.3.

For more information, see XWP Online Help.