The heat pump application configures a minimum supply air flow in the temperature control dead zone. The function can be configured individually for all room operating modes.

Description

Name

Default value

Minimum supply air Comfort

1:Off
2:Minimum ventilation
3:Demand-controlled ventilation
4:Minimum & demand-controlled ventilation

CmfCnf

4:Minimum ventilation & demand-controlled ventilation

Minimum supply air for Pre-Comfort.

PcfCnf

3:Demand-controlled ventilation

Minimum supply air Economy

EcoCnf

1:Off

Minimum supply air Protection

PrtCnf

1:Off

Minimum fan speed for all room operating modes is also configured.

Description

Name

Default value

Minimum fan speed for ventilation

FanSpdMinVnt

50 [%]