The volume flow setpoints for the heating or cooling sequence can be defined independent of one another. The values are not interdependent.

Volume flow
setpoints

VAV volume flow

 

TR

Room temperature

SpH

Effective heating setpoint

 

SpC

Effective cooling setpoint

VavSuAirFlMaxH

Maximum air volume flow heating

 

VavSuAirFlMaxC

Maximum air volume flow cooling

VavSuAirFlMinH

Minimum air volume flow heating

 

VavSuAirFlMinC

Minimum air volume flow cooling

VavSuAflMinVnt

minimum air volume flow for ventilation

 

 

 

Figure: Serial control sequence for a VAV application with different air volumes for heating and cooling

Description

Name

Default value

Supply air VAV maximum air volume flow for cooling

VavSuAirFlMaxC

100 [m3/h]

Supply air VAV minimum air volume flow for cooling

VavSuAirFlMinC

50 [m3/h]

Supply air VAV maximum air volume flow for heating

VavSuAirFlMaxH

100 [m3/h]

Supply air VAV minimum air volume flow for heating

VavSuAirFlMinH

50 [m3/h]

Supply air VAV minimum air flow for ventilation

VavSuAflMinVnt

0 [m3/h]