The HVAC application can also be controlled by presence through the use of a presence detector.

The HVAC application can be configured for each room to react to presence for each room and regardless of the room operating mode.

Description

Name

Default value

Presence operating mode for Comfort

1:None
2:Considered presence
3:Considered absence
4:Considered presence & absence

PscModCmf

4:Considered presence & absence

Presence operating mode Pre-Comfort

PscModPcf

4:Considered presence & absence

Presence operating mode for economy

PscModEco

1:None

Present operating mode for protection

PscModPrt

1:None

The delays for the HVAC application in a room can also be configured for each room.

Description

Name

Default value

Switching delay for presence

SwiDlyPrst

5 min.

Switching delay for absence

SwiDlyAbst

5 min.