The DXR2 room automation station for central weather station, floor level (Cen-Flr) can process measured values for outside temperature, precipitation, wind, and relative air humidity and provides the weather information to the widest range of applications or room operator units.
The function is part of application types for central functions and can be loaded to a DXR2.E/M18.
The following weather information can also be read on the DXR2 for the central weather station, floor level (Cen-Flr):
Sensor | Inputs | Information is used for |
---|---|---|
Outside air temperature | None: Superposed measurement on the automation station on the building level (Cen-Bldg) wins | - - - |
Precipitation | Binary input (NO contact): Local measurement on the automation station, floor level (Cen-Flr) wins against the superposed measurement, building level (Cen-Bldg) | Application: Precipitation protection for awnings |
Wind | 0…10V: Local measurement on the automation station, floor level (Cen-Flr) wins against the superposed measurement, building level (Cen-Bldg) | Application: Wind protection for facade products |
Relative humidity | None: Superposed measurement on the automation station on the building level (Cen-Bldg) wins | - - - |