Valve actuators are operated from time to time to prevent them from seizing after long periods of inactivity (e.g. heating valve during the summer). The valve actuator is controlled to lose as little heating energy as possible.
The central function for the hot water supply chain performs the valve protection function and can be changed in the parameters as needed.
Description | Name | Default value |
---|---|---|
Kick value | KickVal | 50 [%] |
Kick time | TiKick | 2 min |
Kick cycle | KickCyc | 500 h |