The HVAC application can also be controlled by presence through the use of a presence detector.
The HVAC application can be configured for each room to react to the presence signal for each room according to the room operating mode.
The application is programmed to respond to presence and absence of occupants in the room. Occupancy includes scheduled and unscheduled use of the room. BAS scheduling features drive the room operating mode to accommodate scheduled use. An optional presence detector can accommodate unscheduled use. The two sources of data are combined to set the operating state of the HVAC application. The combination of data from two sources is configurable.
By default the application ignores the presence detector during Economy mode and follows it during Comfort mode. For many critical spaces, the opposite behavior is selected: ignore the presence detector during Comfort mode and follow it during Economy. The applicable delays for the HVAC application in a room can also be configured for each room.
Description | Name | Default value |
---|---|---|
Switching delay for presence | SwiDlyPrst | 5 Min |
Switching delay for absence | SwiDlyAbst | 5 Min |