Under static calibration, the values are configured in the application function from the data sheet on the VAV box. Per channel (supply air or extract air), enter two values: Volume flow in m3/h and the associated box coefficient c.

Description

Name

Default value

Nominal air volume flow

AirFlNom

100 [m3/h]

Supply air VAV box coefficient

VavSuBoxCoef

150 [m3/hSqrtPa]