A stage controller can also be configured on the DXR2 room automation station for each aggregate regardless of the room operating modes.
Description | Name | Default value |
---|---|---|
Controller type 0:PID controller | CtrType | 0:PID controller |
Controller values for hysteresis, delay, and number of stages can be configured.
Description | Name | Default value |
---|---|---|
Switch-on value | HysSwiOff | 0.5 K |
Switch-off value | HysSwiOn | 0.5 K |
Delay when switching | SwiDly | 5 min. |
Number of stages | NumSts | 1 |
The following example illustrate the response of the output for a 4-position controller compared to room temperature.
Figure: Example of a 4-stage controller