Plant diagram
Figure: Example for a heated ceiling application 2-pipe system
Key:
DXR2… | Automation station |
| R1 | Room operator unit |
Rcg | Ceiling heating valve |
| D1 | Presence |
CdnMon | Condensation monitor |
| D2 | Window contact |
Sequences
| ||||
Y | Output signal |
| TR | Room temperature |
SpH | Effective heating setpoint |
| SpC | Effective cooling setpoint |
YH | Heating valve |
|
|
|
Figure: Modulating heating sequence