The room operating mode can handed over for distribution to the room using a BACnet reference in the central function. Four groups are available for central functions in one DXR2 for distribution of the room operating mode.

Data point name

Description

Desigo primary application

CenOpModCmdv

Central operating mode command value

1:Protection
2:Economy
3:Pre-Comfort
4:Comfort

PXC {OpMSched3}

Delay function on large facades

Each of the four command groups for the room operating mode can be distributed in the building with a delay using three additional groups. It is used primarily in buildings with larger facades if control influences act on facades for a change to the room operating mode. The delay can be configured.

Description

Name

Default value

Central operating mode delay 1

0...7200 [s]

CenOpModDly1

10 [s]

Central operating mode delay 2

0...7200 [s]

CenOpModDly2

20 [s]

Central operating mode delay 3

0...7200 [s]

CenOpModDly3

30 [s]