The following trends can be configured and enabled for each room:
- Trend room temperature
- Trend room air quality
- Trend relative room air humidity
- Trend room operating mode
- Trend blinds command
Trends are not enabled by default. The enable and trend type must be configured for each enabled trend.
Description | Name | Default value |
---|---|---|
Trend description text | Description | Trend for … |
Type of trend 0:Change-of-Value (COV) | Logging type | Queried |
Polling interval | Logging interval | 90 [s] |
This information can be read and displayed via BACnet client, e.g. Desigo CC.