You can configure how a room is cooled or heated for the plant operating mode on the DXR2 room automation station. The following options are available separately as setting values for heating and cooling:
- Heating with radiators only (radiator, floor heating, ceiling heating)
- Heating with air handling only (heating coils, electric reheaters)
- Heating with both
- Cooling with radiators only (floor cooling, chilled ceiling/beams)
- Cooling with air handling only (cooling coils)
- Cooling with both
Description | Name | Default value |
---|---|---|
Heating comfort 1:None | CmfCnf | 4:Radiator & air handling |
Heating pre-comfort | PcfCnf | 4:Radiator & air handling |
Heating economy | EcoCnf | 4:Radiator & air handling |
Heating protection | PrtCnf | 4:Radiator & air handling |
Heating warm up | WarmUpCnf | 4:Radiator & air handling |
Cooling comfort | CmfCnf | 4:Radiator & air handling |
Cooling pre-comfort | PcfCnf | 4:Radiator & air handling |
Cooling economy | EcoCnf | 4:Radiator & air handling |
Cooling protection | PrtCnf | 4:Radiator & air handling |
Cooling cool down | CoolDnCnf | 4:Radiator & air handling |
Cooling free cooling | FreeCCnf | 4:Radiator & air handling |