Room controller output signals

The room controllers forward their output signals (0…100%) to all impacted aggregates in all segments of the room. For example, the heat controller, that control room temperature, always forwards its output signal to all enabled aggregates including radiators, ceiling heating, and heating coils. In control for the individual aggregates, the 0…100% signal is always converted to the configured output signal.

Figure: Examples of room controllers with 0…100% output signal to the aggregate controllers

Key:

R

Room

 

S

Segment or segments

H

Heating controller

 

RAD

Radiator controller

C

Cooling controller

 

CCG

Chilled ceiling controller

R

IAQ controller

 

VAV

Controller for VAV actuator

F

Air volume flow tracking controller

 

CCL

Cooling coil controller

RH

Humidity controller

 

 

 

Control sequences for temperature control

The sequence for each heating/cooling aggregate can be configured in temperature control of the DXR2. There is one sequence for heating and one sequence for cooling.

The devices are then controlled in the cooling or heating sequence based on room temperature and setpoint. The next sequence element is immediately controlled if a device is currently unavailable (fault or out of service).

 

Figure: Sequence of control sequences for a VAV application

Fan coil application

The control sequences for temperature control in a fan coil application can be adapted through the following parameters:

Description

Name

Default value

Outside air damper cooling sequence

DmpOaCSeq

1

Radiant floor cooling sequence

RfrCSeq

2

Radiant ceiling cooling sequence

RcgCSeq

3

Heating/cooling coil cooling sequence

HCclCSeq

4

Cooling coil cooling sequence

CclCSeq

5

Fan cooling sequence

FanCSeq

6

Radiant floor heating sequence

RfrHSeq

1

Radiator heating sequence

RadHSeq

2

Radiant ceiling heating sequence

RcgHSeq

3

Heating/cooling coil heating sequence

HCclHSeq

4

Heating coil heating sequence

HclHSeq

5

Fan heating sequence

FanHSeq

6

VAV application

The control sequences for temperature control in a VAV application can be adapted through the following parameters:

Description

Name

Default value

Radiant floor cooling sequence

RfrCSeq

1

Radiant ceiling cooling sequence

RcgCSeq

2

Heating/cooling coil cooling sequence

HcclCSeq

3

Cooling coil cooling sequence

CclCSeq

4

VAV cooling sequence

VavCSeq

5

Radiant floor heating sequence

RfrHSeq

1

Radiator heating sequence

RadHSeq

2

Radiant ceiling heating sequence

RcgHSeq

3

Heating/cooling coil heating sequence

HCclHSeq

4

Heating coil heating sequence

HclHSeq

5

VAV heating sequence

VavHSeq

6

Fan-powered box

The control sequences for temperature control in a fan-powered box application can be adapted through the following parameters:

Description

Name

Default value

Radiant ceiling cooling sequence

RcgCSeq

1

Heating/cooling coil cooling sequence

HcclCSeq

2

Cooling coil cooling sequence

CclCSeq

3

Fan cooling sequence

FanCSeq

4

VAV cooling sequence

VavCSeq

5

Radiator heating sequence

RadHSeq

1

Radiant ceiling heating sequence

RcgHSeq

2

Heating/cooling coil heating sequence

HCclHSeq

3

Heating coil heating sequence

HclHSeq

4

Fan heating sequence

FanHSeq

5

VAV heating sequence

VavHSeq

6

Heat pump application

The control sequences for temperature control in a heat pump application can be adapted through the following parameters:

Description

Name

Default value

Outside air damper cooling sequence

DmpOaCSeq

1

Radiant ceiling cooling sequence

RcgCSeq

2

Heating/cooling coil cooling sequence

HCclCSeq

3

Fan cooling sequence

FanCSeq

4

Radiator heating sequence

RadHSeq

1

Radiant ceiling heating sequence

RcgHSeq

2

Heating/cooling coil heating sequence

HCclHSeq

3

Heating coil heating sequence

HclHSeq

4

Fan heating sequence

FanHSeq

5