You can discover and edit existing schedule and calendar objects in Siemens field panels. This procedure assumes you have existing schedule and calendar objects in a Compact or Modular controller.
NOTE:
When you create or edit a calendar object, there are four data types you can choose from; Date, Date Range, Week and Day or Custom. You are able to use the first three data types if you are not using wildcard entries, however, the Custom data type is not available at this time.
- From the Nav pane, select and expand Hierarchy, Apps, Schedules, and then select schedule or calendar object.
- Double-click the selected schedule or calendar.
- The schedule displays in the Schedule Editor window/view.
- From the upper-right corner, select the Edit Schedule drop-down menu, and then select Edit Schedule.
- Enter the modifications you wish to make for the schedule or calendar, and then click Save.
If editing a calendar and entering the wildcards for a holiday, the holiday dates will overwrite the field panel’s calendar object. This is visible through BACnet Object browser or other application such as Field Panel Web UI (FP Web).