The following logos can be customized:
- The logo displayed on the logon screen.
- The logo displayed in the header of the work area.
Customizing the Logon Screen Logo
This procedure customizes the logo displayed on the login screen. By default, when you login to the station using an Operator View (browser window), the Siemens logo displays.
For more information, see the Tridium Web site for supporting documentation.
- You have created and saved a custom image you want to use on the logon screen.
Note: The file must be named logo.jpg.
- Copy your logo image to the file system of the station. The typical path is C:\Users\[your user name]\Niagara4.x\tridium<StationName>\shared.
- Rename the existing logo.jpg file. For example, logo_old.jpg.
- In the Nav pane, drag your logo image from My File System\UserHome\Stations\<StationName>\shared folder and drop it in the station Files folder.
- Restart the station and then logon through the Operator View (browser window) to view your customized logon screen.
Customizing the Header Logo
This procedure customizes the logo displayed in the header of the work area.
For more information, see the Tridium Web site for supporting documentation.
- You have created and saved a custom image you want to use in the header of the work area.
Note: The header logo file must be named headerLogo.jpg.
- Copy your header logo image to the file system of the station. The typical path is C:\Users\[your user name]\Niagara4.x\tridium<Station Name>\shared.
- Rename the existing headerLogo.jpg file. For example, headerLogo_old.jpg.
- In the Nav pane, drag your header logo image from My File System\UserHome \Stations\<StationName>\shared folder and drop it in the station Files folder.
- Restart the station and then open an application to see the customized header.