Applications 6622 and 6602 have a special virtual point, Baseboard Rad, that determines whether or not a radiator displays.
Application 6654 displays a damper or a valve depending on the value of the MTR TIMING point.
A MTR TIMING value of 124 and lower displays a damper.
A MTR TIMING value of 125 and higher displays a cooling valve.
In order for an RDY device to work with a schedule that is defined in the station or another device, do not set the value of Parameter 107 to Disabled. Otherwise, the ScheduleMode object will not be commandable, and Room Mode will not change to the value that ScheduleMode is commanded to.
For a BT300 drive, use the drive keypad to set the Field Bus Control and Field Bus Reference functions to any value other than the Fieldbus value. This allows these functions to command the BT300 drive in and out of fieldbus mode using the Niagara N4 interface.
The MD Series power meters have a series of virtual points to configure the analog gauges on the graphic.
Commanding Max Volts and Max Amps determines the range of the gauges.
Commanding Ampere Ticks and Volt Ticks configures the number of steps from the zero (0) value to the maximum value.