NOTE:
Only complete this procedure if the configuration does not use a Siemens field panel. For example, if FLN devices are connected directly to MS/TP ports of the N4 / TNMcontroller.
It is recommended that you restart the station after adding a N4 / TNMcontroller.
If the N4 station is acting as both a supervisory controller and an air handling unit controller, see the topic Adding a LocalDeviceAhu object to the station in Advanced Topics.
In previous revisions, you had to add tags and relations manually to the Local Station object in order to use the BacnetNetwork LocalStation object as a virtual field panel or AHU controller. With Revision 1.10.xxx and later, templates are provided for LocalDeviceTc and LocalDeviceAhu virtual devices, which eliminates the need to manually add tags and relations.
This section outlines the following topics:
- Determining if a Station Local Device is Needed
- Configuring the Station Local Device, if one is necessary.