Siemens_Day_Ngt_Schedule
To create additional schedules intended for use with PTEC/ATEC DAY.NGT points, duplicate Config/Siemens_Schedules/Siemens_Day_Ngt_Schedule and configure as necessary. Duplicating an existing schedule will assure that the new schedule has the correct tagging and enumerated value range. The new schedule will also use the same special event calendar as the original.
Do not under any circumstances change the range facet on the schedule’s Properties tab. Doing so will cause the schedule to work improperly. Also, do not remove the sie:dayNightSchedule tag. Doing so will keep the new schedule from appearing in the BacnetDeviceManager wizard (see the section Tagging and Auto-Linking to New PTEC/ATEC Devices).
Siemens_OpMode_Schedule
To create additional schedules intended for use with System ONE ROOM_OP_MODE points (Schedule_Mode for RDY devices), duplicate Config/Siemens_Schedules/Siemens_OpMode_Schedule and configure as necessary. Duplicating an existing schedule will assure that the new schedule has the correct tagging and enumerated value range. The new schedule will also use the same special event calendar as the original.
Do not under any circumstances change the range facet on the schedule’s Properties tab. Doing so will cause the schedule to work improperly. Also, do not remove the sie:opModeSchedule tag. Doing so will keep the new schedule from appearing in the BacnetDeviceManager wizard (see the section Tagging and Auto-Linking to New DXR Devices).
Other Schedules
To create schedules for other purposes, create a new folder under Config and copy a schedule of the appropriate type from the schedule palette to the new folder. Configure the new schedule as necessary. See the document DocScheduling in Niagara Help for instructions.