Adding a BACnet network and Siemens utilities to the station You are connected to the station.
In the Nav pane, expand Station > Config > Drivers .
From the menu bar, select Window > Side Bars > Palette .
To add the BACnet network. NOTE: Do this only if you are not using templates.
In the Palette pane, click Open and type bacnet in the filter field.
Select the bacnet module and click OK .
Drag-and-drop BacnetNetwork from the Palette pane onto Drivers in the Nav pane and click OK .
To add the Siemens Utilities Service :
In the Palette pane, click Open and type sie in the filter field.
Select the SieUtilities module and click OK .
Drag-and-drop SieUtilitiesService from the Palette pane onto Services in the Nav pane and click OK .
In the Nav pane, right-click the station and select Save station .
The configuration is complete and saved.