This section covers the steps required to update a Siemens N4 Appliance version 1.10 station to version 3.00.
NOTICE
Save a copy of your current Siemens Appliance 1.10 station!
Always use Station Copier to save a copy of your current Siemens Appliance 1.10 station before executing the upgrade procedure.
Complete the procedure Before Installing the Siemens N4 Appliance before performing these steps.
- Update Modules in the JACE
a. Open the JACE platform (not the Supervisor platform) and use Platform/Software Manager to copy modules to the JACE platform.
b. Click Upgrade.
c. Scroll down to find the siemensAppliance. (Select the following files: siemensAppliance-rt/ux/wb), sieUtilities, and if not previously installed, haystack-rt, bacnetUtil-rt, and dashboard-rt/ux/wb.
d. Click Commit. The new modules are sent to the JACE.
- Restart the Station
Open Platform/Application Director and restart the new station.
- Install the Station Update Files. The station update files are used by the JACE station to create a Siemens N4 Appliance 3.00 station. In File Transfer Client:
a. In the left pane, under “Files on this computer”, locate and open the Siemens_N4_Appliance_3_00_100/UpdateFiles folder as shown in the following Figure. Move the cursor over the path configuration box to display the selected path. If you cannot find the Siemens_N4_Appliance_3_00_100 folder, review the first section of this document.
b. In the right pane, under Files on “[station_id], locate and open /home/niagara/shared. Your File Transfer Client view should look similar to the view shown in Figure 9, Transferring the Siemens_Update Folder.
c. Click the arrow pointing to the right to copy the folder and its contents. You should then see a Siemens_Update_3_00 folder in the right pane.
- Add Services
a. Log in to the restarted station.
b. From the Palette sidebar, open the sieUtilities palette and drag SieUpgradeStation into the station’s Config/Services folder.
- Upgrade the Station
Right-click on the SieUpgradeStation service and select Actions/Sie Upgrade Station.
- The station is converted to an N4 Appliance station.
- Restart the Station
Open Platform/Application Director and restart the new station.
- The Installation is now complete.
To update installed devices to Siemens N4 Appliance 3.00 templates, see section 8.