Existing Schedules
The Siemens N4 Appliance Schedule Editor in Operator View is a browser-hosted editor that allows you to view and edit pre-existing Niagara schedules created using Siemens Workbench. The following schedule types are supported:
- Local schedules that run in the station, independent of Schedule objects in BACnet devices.
- Local schedules that run in the station and are linked to Schedule objects in BACnet devices by the BACnet Schedule Export Manager. When the schedule editor modifies a local Niagara schedule that is linked to a BACnet schedule by the Export Manager, all linked BACnet schedules are updated.
NOTE:
When you create or edit a calendar object, there are four data types you can choose from; Date, Date Range, Week and Day or Custom. You are able to use the first three data types if you are not using wildcard entries, however, the Custom data type is not available at this time.
NOTE:
Using the every year wildcard will result in an error when synchronizing with the Siemens field panel.
Schedule Selection
Appliance schedules are found in the Apps/Schedules folder. Selecting any of these schedules opens the Schedule Editor in Operator View.
Schedule Editor in Operator View
The Schedule Editor in Operator View is a standard N4 Appliance template view with the native N4 schedule editor in the View pane.
Weekly Schedule Tab
Special Events Tab