Navigate to Station > Config > Drivers > BacnetNetwork > [PTEC device]
Expand the PTEC device, and double click on siePtecPointTable.
The PTEC Point Editor table displays, showing all custom points (user-defined BACnet objects) in the PTEC device.
Click the + button at the bottom right of the PTEC Point Editor window.
A new row displays in the PTEC Point Editor table. The new row is configured for an AO type point by default:
Enter the new PTEC point information.
To check the Syntax at any point, select Syntax Check.
Click Save.
Click Yes at the "Press OK to Proceed Saving?" prompt
For PTEC, a point added by the Point Editor is not automatically added to the N4 point folder. Use the standard N4 point discover/add functions to add it to the N4 station.