Discovering BACnet Devices

  • Siemens Workbench is open.
  1. In the Nav pane, expand Station > Config > Drivers.
  1. Double-click BacnetNetwork to display the Bacnet Device Manager.
  1. Click Discover at the bottom of the Database pane.
  • The Configure Device Discovery dialog box displays.
  1. Update the following fields:
  • Device Low Limit and Device High Limit: Enter a range of device instance numbers for the discovery process.
  • Networks: Select individual check boxes to limit the discovery to certain networks or select the Send Global check box to discover devices on all connected BACnet networks.
  • NOTICE! The first time you perform the Discovery procedure, you must select the Send Global check box. After the first successful discovery, discovered BACnet networks are preselected, and it’s generally not required to select the Send Global check box again.
  1. Use the default setting for Wait Response Time and click OK.
  • A progress bar displays during the discovery process.
  • The Discovered list of devices displays when the process is complete.