To modify an existing point in a PXC, you must first add the point to the N4 database, and then run SieUpdateDb, which will allow you to edit the point.
To add a point:
- Navigate to Station > Config > Drivers > BacnetNetwork > [PXC / TC Device] > Points.
- Double-click on Points.
- Click Discover.
- Find and select to highlight the desired point.
- Click Add.
If you need to rename a point, perform sieUpdateDb in the next steps first, and then make the change.
● Navigate to Station > Config > Services > SieUtilitiesService.
● Right-click on SieUtilitiesService and select Actions > SieUpdateDb.