The default Hierarchy is provided so that you can rename the Site and Area names and create new sites and areas.
You can customize hierarchies by adding/duplicating an area or site in the hierarchy. You do this by using the duplicate function.
NOTE:
Site names can be renamed.
You can also duplicate sites using this procedure, except you do not have to perform Steps 2 and 3. When you duplicate a site, you will also need to duplicate the Siemens Summary View for the areas that were duplicated along with the site as described in Steps 4 through 11.
To Add an Area in the Hierarchy
- From the Nav pane, expand Config, Siemens_Site, Demo_Site and then select and right-click an area of the site (for example, West Wing) and then select Duplicate.
- The Name dialog box displays.
- Enter a name (for example, North Wing) for the area you are adding. Click OK.
- Right-click the new area you added, and select Relation Mark.
- Navigate to Station, Files, px, Siemens_Site_Views, and then expand Siemens_Site_Views.
- Duplicate the [Original Area Summary Name.px] and assign a [New Area Summary Name.px].
- Navigate to Station, Config, Siemens_Site, and expand Siemens_Site [Site Name].
- Right-click the new [Area Name] and select AX Property Sheet.
- Expand Summary View, Px View.
- Change the Px File to the new px file you created in Step 5, using the File Ord Chooser or typing the file name.