To modify a PTEC point, complete the following:
- The Station is open.
- Navigate to Station > Config > Drivers > BacnetNetwork > [PTEC Device]
- Expand the PTEC device, and double click on the siePtecPointTable.
- The PTEC Point Editor table displays, showing all custom points (user-defined BACnet objects) in their PTEC device.
- Modify point(s) in the table as desired.
- To check the Syntax at any point, select Syntax Check.
- Click Save and Yes in the ensuing pop-up window.