Delete a point from the N4 database and from the device
- The platform and station are open.
- In the Nav pane, expand Station > Config > Drivers > BacnetNetwork > [device] > Points.
- The points in the N4 database are displayed.
- Right-click the point you want to delete and select Views > Sie Delete PX Point.
- The point is removed from the N4 database and the device.
Delete a point from the N4 database but leave it in the device
- The platform and station are open.
- In the Nav pane, expand Station > Config > Drivers > BacnetNetwork > [device] > Points.
- The points in the N4 database are displayed.
- Right-click on the point you want to delete and select Delete.
- The point is removed from the N4 database.
NOTE: If you want to delete a point from the device that is not in the N4 database, complete the following:
- Discover the point
- Run Sie Update Db
- Delete the point (Views > Sie Delete Px Point)