- Select File from the drop-down menu and select Open Platform.
- Enter the IP address of the N4 Appliance Controller in the dialog box and select OK.
- If prompted to verify a certificate, select OK.
- In the list of platform views, double-click Platform Administration to access those tools.
- In the platform administration window, select the Commissioning button.
- In the Commissioning Dialog, make the following selections:
- De-select or Select the license option, depending on if a license has been deployed.
- Unselect Lexicons.
Lexicons allow user to view Workbench in other languages, you may install them if you wish.
- Ensure synch with my local system date and time is selected.
- Deselect Configure TCP/IP.
- Click Next.
- For Enable Runtime profiles, select UX and WB.
- When prompted to choose a station to install on the Jace, select the station you created in the previous procedure.
- Select Auto Start and Start After Install.
- If asked for a passphrase enter one.
- Select copy Every File in the Station Directory and Subdirectories
- In the Software Installation dialog, if Upgrade All Out of Date is disabled, select Next. If Upgrade All Out of Date is enabled, select it.
- Select Next.
- In the Distribution File Installation, select Next
- Change the passphrase, if required.
- Change platform username and password, if required. Click Next.
- In the Review Changes dialog box, click Finish.
- Wait for the station to start. It can take 2 to 5 minutes.
- Connect to the platform and station with new passwords.