The following communication objects are used to control the "Direct operation” function:
A Direct operation lock
No. | Object name | Function | Datapoint type | Flags |
---|---|---|---|---|
58 | A Direct operation lock | On/Off | 1.003 enable | CW |
Function:
This communication object can be used to lock this channel or enable direct operation (operation directly on the device).
Example:
Enabling of direct operation through a key switch.
Note:
When the bus voltage returns, the setting is reset and operation on the device is enabled.
Availability:
The "A Direct operation lock ” communication object is displayed if the following configurations have been made:
- Parameter "Function channels A + B” on the "device settings” parameter card
- Setting: "Single” or "Pairwise"
- Parameter "Direct operation” on the “functions, objects” parameter card
- Setting: “enable”
- Parameter "Direct operation lockable” on the “functions, objects” parameter card
- Setting: “enable”
More information:
A status direct operation
No. | Object name | Function | Datapoint type | Flags |
---|---|---|---|---|
58 | A status direct operation | On/Off | 1.002 Boolean | CRT |
Function:
This communication object is used to report whether direct operation is activated.
Note:
After bus voltage recovery, direct operation is deactivated.
Availability:
The “A status direct operation” communication object is displayed if the following configurations have been made:
- Parameter "Function channels A + B” on the "device settings” parameter card
- Setting: "Single” or "Pairwise"
- Parameter "Direct operation” on the “functions, objects” parameter card
- Setting: “enable”
- Parameter "Direct operation lockable” on the “functions, objects” parameter card
- Setting: “enable”
More information: