The following communication objects are used to control the "Dimming” function:
A + B Switching
A Switching
No. | Object name | Function | Datapoint type | Flags |
---|---|---|---|---|
5
| A + B Switching A Switching | Off On/Off On/Off | 1.001 switch | CRWT |
Function:
Switching telegrams are sent via the group address linked with this communication object.
Availability: Communication object “A + B Switching”
The "A + B Switching” communication object is displayed if the following configurations have been made:
- Parameter "Function channels A + B” on the "device settings” parameter card
- Setting: “Single”
- Parameter "Function channel” on the “functions, objects” parameter card
- Setting: "Switching” or "Dimming"
Availability: Communication object “A Switching”
The "A Switching” communication object is displayed if the following configurations have been made:
- Parameter "Function channels A + B” on the "device settings” parameter card
- Setting: “Pairwise”
- Parameter "Function channels” on the “functions, objects” parameter card
- Setting: “Dimming”
More information:
A Dimming
No. | Object name | Function | Datapoint type | Flags |
---|---|---|---|---|
8 | A Dimming A + B Dimming | darker brighter/darker brighter/darker | 3.007 dimming control | CRWT |
Function:
The dimming telegrams are sent via the group address linked with this communication object.
Availability: Communication object “A Dimming”
The "A Dimming” communication object is displayed if the following configurations have been made:
- Parameter "Function channels A + B” on the "device settings” parameter card
- Setting: “Single”
- Parameter "Function channel” on the “functions, objects” parameter card
- Setting: “Dimming”
Availability: Communication object “A + B Dimming”
The "A + B Dimming” communication object is displayed if the following configurations have been made:
- Parameter "Function channels A + B” on the "device settings” parameter card
- Setting: “Pairwise”
- Parameter "Function channels” on the “functions, objects” parameter card
- Setting: “Dimming”
More information: