With the "Sequenced switching group control” function, for example, 2 or 3 lamps can be switched on and off in succession with a single push-button. Lamp groups can also be switched instead of lamps. The sequence of the circuits is determined via the assigned communication objects and cannot be changed via parameters.
If there are several push-buttons with the "Sequenced switching group control” setting for the same lamps, switching is performed independently from each push-button. This means that the push-button switches the switching sequence that is next for it, regardless of which switch command another push-button sent last.
The prerequisite for this function is that the "Single” option is selected in the device settings for the channel concerned.
“Function of channels A + B” parameter
Application example
Step-by-step switching on and off of lamp groups of a chandelier or another lamp with multiple lamp groups.
Switching sequence 2 switching groups
Push-button pressure | Status of lamp 1 | Status of lamp 2 |
---|---|---|
1 | ● | ○ |
2 | ● | ● |
3 | ○ | ● |
4 | ○ | ○ |
● | Switched on | |
○ | Switched off |
Switching sequence 3 switching groups
Push-button pressure | Status of lamp 1 | Status of lamp 2 | Status of lamp 3 |
---|---|---|---|
1 | ● | ○ | ○ |
2 | ○ | ● | ○ |
3 | ● | ● | ○ |
4 | ● | ● | ● |
5 | ○ | ● | ● |
6 | ● | ○ | ● |
7 | ○ | ○ | ● |
8 | ○ | ○ | ○ |
● | Switched on | |
○ | Switched off |