The signals arriving at the input channels of the binary input are processed in the following sequence:
1 | 2 | ||
3 | 4 | ||
5 |
First, the signal arriving at the binary input from the connected hardware (e.g. a sensor or push-button) is evaluated. If direct operation is active, this signal is ignored and the signal arriving at the binary input via the direct operation push-button is valid. If an inversion is configured, the signal is inverted. Then it is checked if a lock is active for this channel. If no lock is active, the other parameters that have been configured for this channel are evaluated (e.g. functions such as “switching", “dimming", “solar protection control", ...).