LTE Mode was specifically designed to simplify engineering. Unlike with S-Mode, there is no need to create the individual connections (group addresses) in the tool. The devices autonomously establish connections.

Definitions

To make this possible, the following circumstances are predefined:

  • Every device or subdevice is located within a zone

  • Every data point (input or output) is assigned to a zone

  • Every data point (input or output) has a precisely defined "name".

Whenever an output and an input with the same "name" are located in the same zone, a connection is established automatically, as shown in the following diagram.

3171Z2en_01

Engineering and commissioning

  • For a detailed description of KNX (topology, bus supply, function and setting of LTE zones, filter tables, etc.), see "Communication via the KNX bus for Synco 700, 900 and RXB/RXL, Basic Documentation" [6].

  • LTE Mode data points and settings are described in the Synco Application Manual [12].

  • To engineer and commission a specific system, use the Synco700 planning and commissioning protocol (XLS table in HIT, [7]).