Operation PT1001-A1Activate the alarm
- Press the red <Start Voice Alarm> indicator button.
- The red <Start Voice Alarm> indicator button is active
Reset the alarm manually
- Press the black <Reset Voice Alarm> indicator button.
Silence the alarm manually
- Press the green <Silence Voice Alarm> indicator button.
- The green <Silence Voice Alarm> indicator button is active.
Reset the latching fault message
- The 'Fault' LED lights up.
- The fault in the system has been rectified.
- Press the black <Reset Fault> button.
- The fault message is reset.
Silence an active buzzer
- Press the black <Silence Buzzer / LED Test> button.
- The buzzer is activated again on a new event.
Recur fault messages
- The 'Fault' LED lights up again.
- The fault in the system has not been rectified.
- Inform Siemens customer support.
- Request that maintenance be carried out by technical personnel.
Perform a LED test
- Press and hold the black <Silence Buzzer / LED Test> button for a few seconds to test the function of the buzzer and the LEDs.