Transmit a manual announcement / Trigger an evacuation with a manual announcement
The manual announcement function of the PT2002-A1 depends on the configuration and the hardware and software versions.
Variant A: without using the hook-off switch
- Use the PACE-Design MP2.0 SR2 or later versions
- Use the PT2002-A1 FS03 or later versions, or upgrade the older PT2002-A1 according to 'MI Cerberus PACE Compact Fire Fighter Call Station - Switch at Microphone Hook'
- The PT2002-A1 is configured without using the hook-off switch and with the <Push-To-Talk> button configured as 'All call'.
- Remove the microphone from the housing.
- No action.
- Press the <Push-To-Talk> button on the microphone and hold it while talking into the microphone at a normal sound level.
- All zones are selected for this alarm message.
- Active announcements and background music are deactivated.
- If configured, a pre-announcement message is played and the engaged LED <BESETZT> is active.
- The microphone is activated.
- A manual announcement is made in all zones.
- Release the <Push-To-Talk> button after the announcement.
- The microphone is deactivated.
- All zones are deselected.
- Another announcement can be performed when you press the <Push-To-Talk> button again. If so, jump to step 2.
- Put the microphone back in the housing.
- No action.
Notes:
- If the microphone is not or not correctly put back to the microphone holder during the configured timeout, a fault will be displayed.
- An additional announcement can be performed when you press the <Push-To-Talk> button again. If so, jump to step 2.
Variant B: using the hook-off switch (according to the Austrian standard F3033)
- Use the PACE-Design MP2.0 SR2 or later versions
- Use the PT2002-A1 FS03 or later versions or upgrade the older PT2002-A1 according to 'MI Cerberus PACE Compact Fire Fighter Call Station - Switch at Microphone Hook'
- The PT2002-A1 is configured according to the Austrian standard F3033 or using the hook-off switch.
- Remove the microphone from the housing.
- All zones are selected for this alarm message.
- Press the <Push-To-Talk> button on the microphone and hold it while talking into the microphone at a normal sound level.
- Active announcements and background music are deactivated.
- If configured, a pre-announcement message is played and the engaged LED <BESETZT> is active.
- The microphone is activated.
- A manual announcement is made in all zones.
- Release the <Push-To-Talk> button after the announcement.
- The microphone is deactivated.
- Another announcement can be performed when you press the <Push-To-Talk> button again. If so, jump to step 2.
- Put the microphone back in the housing.
- All zones are deselected.
Notes:
- If the microphone is not or not correctly put back to the microphone holder during the configured timeout, a fault will be displayed.
- An additional announcement can be performed when you press the <Push-To-Talk> button again. If so, jump to step 2.
Variant C: restricted variant B
- Use any PACE-Design MP2.0 SR1 or later versions
- Use the PT2002-A1 ES01
- The PT2002-A1 is configured according to the Austrian standard F3033 or using the hook-off switch.
- Remove the microphone from the housing.
- All zones are selected for this alarm message.
- Press the <Push-To-Talk> button on the microphone and hold it while talking into the microphone at a normal sound level.
- Active announcements and background music are deactivated.
- If configured, a pre-announcement message is played and the engaged LED <BESETZT> is active.
- The microphone is activated.
- A manual announcement is made in all zones.
- Release the <Push-To-Talk> button after the announcement.
- The microphone is deactivated.
- Another announcement can be performed when you press the <Push-To-Talk> button again. If so, jump to step 2.
- Put the microphone back in the housing.
- All zones are deselected.
Notes:
- If the microphone is not or not correctly put back to the microphone holder during the configured timeout, no fault will be displayed, the zones will not be deselected, and the additional announcement can not be performed.
- Before you can perform an additional announcement, you need to put the microphone back to the microphone holder.
Play a recorded announcement / Trigger an evacuation with a recorded announcement
- Press a button labeled with the required announcement.
- An alarm is triggered.
- Active announcements are deactivated in all zones.
- The announcement is made in all zones.
- With the corresponding configuration, the announcement is also emitted via the integrated speaker.
- The announcement is continually repeated.
- Press the reset button <RÜCKSTELLEN/AKUSTIK AB> to end the announcement.
Reset a fault message
- The fault LED <STÖRUNG> lights up.
- Press the reset button <RÜCKSTELLEN/AKUSTIK AB>.
- The fault LED <STÖRUNG> turns off.
- The fault in the system has been rectified.
- The fault message is reset.
Recur fault messages
- The fault LED <STÖRUNG> lights up again.
- The fault in the system has not been rectified.
- Inform Siemens customer support.
- Request that maintenance be carried out by technical personnel.