- Select
> System Integrator Apps > DB Builder
.
- Expand the Tag Bundlestree.
- Click +.
- Use the following table to complete the Add Tag Bundle dialog box, and then click Apply.
Field | Description |
Name (required) | Name for the tag bundle. |
Description (optional) | Describe what this tag bundle is for. |
Allow Filter (optional) | Specify which records this will run against and apply/remove the tags. |
Tags to Add (optional) | Specify what tags to apply to the point records. The allowProgram marker tag is required to allow a program to run on points. Otherwise, the program can only run on equips. |
Tags to Remove (optional) | Specify what tags to remove on the point records, if any. |
Config Type (required for Alarm Config) | Specify what type of bundle this would be for. |
Point Kind (required) | Select which point type this bundle is for. Controls the display of the bundle in the Alarm Config app for the appropriate point type. |
Track Bundle (optional) | Set this switch ON to track the bundle. This option adds a tag based on the selection made for Config Type. If Alarm is selected for Config Type, an alarmConfig tag is added to the point record and the name of tag bundle(s) being used by that point is listed. If None is selected for Config Type, a bundles tag is added. If History is selected for Config Type, a historyConfig tag is added, and so on. |