In the Graphics view, there are four programmed features:

  • Actions
  • Status
  • Selection

Direct Hyperlink

  • If you are interested in the extra bubbles due to the extra click, hold down Alt and select the zone/area that has a hyperlink.
    • This will go directly to that hyperlink instead of displaying the bubbles.
      This is only for Desktop view.

Reverse Magic Bubbles - Direct Hyperlink by Default

  • If you would rather have a direct hyperlink as the default and using Alt to get the magic bubbles.
    • This behavior can also be set as default by adding reverseMagicBubbles marker tag.

Actions

This auto looks at points that have the actions tag, and adds on the smartLabel to indicate it can be commanded, and when selected, points actions displays.

Graphics, RAD, RAD point actions

Status

  • Status was created to look at the point status. If commanded, the smartLabel and component are bound by that point glow.
  • Status can also be found on the smartLabel itself.
  • On a floorplan, the status of a point will also pass through on the zone.
  • If it is commanded or in fault, it displays like the screen capture.
    If not, it is based on the legend gradient.
Graphics app, example overridden point.

Selection

When you move the cursor over a smartLabel, it displays the number of alarms and points overridden.