In order to sync the schedules to BACnet (to be read and written), import the schedule points into the data base.
How to sync BACnet Schedules
- Drag the schedule point(s) to DB Builder.
- Click to make the point schedulable.
- Add the point to the schedule.
- If you do not already have a connTuning Policy on the point, create a tuning policy for the point that has Write Schedule enabled. The tuning policy should only be specific to these points.
How to create one is explained here.
Make sure to enable Write Schedule or manually add the writeSchedule tag on the policy.
- The schedule syncs whenever there is a change of value.