Use the Update BACnet CUR from Description tool when you need to update an application that has been modified from the standard template. This tool updates your changes into the template so your sub-points remain connected.
WARNING
Using the tool resets the Room Temp and Room Temp Effective settings. After using this tool, you will have to manually edit every Room Temp and Room Temp Effective setting in all applications that you want to update.
- In the tree view, expand Connectors > BACnet.
- Highlight the connector.
- Click .
- The Tools window will open. Click Update Bacnet Cur from Description.
- Click Apply.
- Navigate back to your application. Check the Room Temp and Room Temp Effective settings.
- If your Room Temp and Room Temp Effective settings are correct, your application has been updated successfully.
- If your Room Temp and Room Temp Effective settings are incorrect, proceed to the next step.
- On the same line as Room Temp or Room Temp Effective, click .
- The Property Editor window will open. In the bacnetCur line, manually enter the setting that should be mapped to that value.
- Click Apply.
- Refresh the application.
- Your application is now updated.