The Create History Sync Jobs tool auto-creates jobs to sync histories to Niagara. It also staggers the jobs in intervals of 50 points at a time so the station is not overloaded when pushing the histories.
- Expand the Connectors Tree and select a connector.
- Click Tools .
- The Tools dialog box displays.
- In the Tools dialog box, select Create History Sync Jobs.
- The Create History Sync Jobs dialog box displays with the number of points synced.
- Click Apply.
Syncing Older Data
The Syncing Older Data tool starts syncing the data starting from the day it is run. It does not sync the previous history data. If you would like to sync previous history data, run a query or job, depending on how much history data you want to sync.