Unit Heater - Points and Associated Tags
Description | Point Name navName | Tags | Point Type | UoM |
Occupied Mode | Occ | occupied, cmd | Bool | Occ/UnOcc |
Fan Command | FanCmd | fan, run, cmd | Bool | On/Off |
Fan Status | FanSts | fan, run, sensor | Bool | On/Off |
Fan Speed | FanSpeed | fan, speed, cmd | enum | Off/Low/Med/High |
Hot Water Valve | HWVlvPos | hot, water, valve, cmd | Num, 0 | % |
Zone Temperature | ZoneTemp | zone, air, temp, sensor | Num, 1 | F °C |
Zone Temperature Setpoint (effective) | ZoneTempSp | zone, air, effective, temp, sp, | Num, 0 | F °C |
Occupied Heating Setpoint | OccHeatSp | occ, heating, zone, air, temp, sp, | Num, 0 | F °C |
Unoccupied Heating Setpoint | UnoccHeatSp | unocc, heating, zone, air, temp, sp, | Num, 0 | F °C |
Fan Coil Unit - Points and Associated Tags
Description | Point Name navName | Tags | Point Type | UoM |
Occupied Mode | Occ | occupied, cmd | Bool | Occ/UnOcc |
Chilled Water Valve | ChWVlvPos | chilled, water, valve, cmd | Num, 0 | % |
Discharge Air Temperature | DaTemp | discharge, air, temp, sensor | Num, 1 | F °C |
Fan Command | FanCmd | fan, run, cmd | Bool | On/Off |
Fan Status | FanSts | fan, run, sensor | Bool | On/Off |
Fan Speed | FanSpeed | fan, speed, cmd | enum | Off/Low/Med/High |
Hot Water Valve | HWVlvPos | hot, water, valve, cmd | Num, 0 | % |
Zone Temperature | ZoneTemp | zone, air, temp, sensor | Num, 1 | F °C |
Zone Temperature Setpoint (effective) | ZoneTempSp | zone, air, effective, temp, sp, | Num, 0 | F °C |
Occupied Cooling Setpoint | OccCoolSp | occ, cooling, zone, air, temp, sp, | Num, 0 | F °C |
Occupied Heating Setpoint | OccHeatSp | occ, heating, zone, air, temp, sp, | Num, 0 | F °C |
Unoccupied Cooling Setpoint | UnoccCoolSp | unocc, cooling, zone, air, temp, sp, | Num, 0 | F °C |
Unoccupied Heating Setpoint | UnoccHeatSp | unocc, heating, zone, air, temp, sp, | Num, 0 | F °C |
Fan - Points and Associated Tags
Description | Point Name navName | Tags | Point Type | UoM |
Fan Command | FanCmd | fan, run, cmd | Bool | On/Off |
Fan Status | FanSts | fan, run, sensor | Bool | On/Off |
Fan Speed | FanSpeed | fan, speed cmd, | enum | Off/Low/Med/High |
Fan VFD Speed | FanVFDSpd | fan, speed, cmd | Num, 0 | % |
Fan VFD Frequency | FanVFDFreq | fan, freq, sensor | Num, 0 | Hz |
Fan Meter - Points and Associated Tags
Description | Point Name navName | Tags | Point Type | UoM |
VFD Energy Total (accumulated) | VFDEnergy | fan, elec, energy, total, point | Num, 0 | kWh |
VFD Power Total | VFDPower | point, fan total, power, active, elec | Num | kW |
Air Handling Unit (US and SI)- Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM - US and SI |
General Points |
|
|
|
|
Occupied Mode | Occ | occupied, cmd | Bool | Occ/UnOcc |
Building Static Pressure | BldgPress | building, air, pressure, sensor | Num, .01 | in w.c. Pa |
Building Static Pressure Setpoint | BldgPressSp | building, air, pressure, sp | Num, .01 | in w.c. Pa |
Filters |
|
|
|
|
Filter Status | FilterSts | filter, run, sensor | Bool | Ok/Dirty |
Filter Pressure Delta | FilterPressDelta | filter, pressure, delta, sensor | Num, .01 | in w.c. Pa |
Single Direct Zone Points |
|
|
|
|
Zone CO2 | ZoneCO2 | zone, co2, sensor | Num, 0 | ppm |
Zone CO2 Setpoint | ZoneCO2Sp | zone, co2, sp | Num, 0 | ppm |
Zone Pressure | ZonePress | zone, air, pressure, sensor | Num, .01 | in w.c. Pa |
Zone Pressure Setpoint | ZonePressSp | zone, air, pressure, sp | Num, .01 | in w.c. Pa |
Zone Temperature | ZoneTemp | zone, air, temp, sensor | Num, 1 | F °C |
Zone Temperature Setpoint (effective) | ZoneTempSp | zone, air, temp, sensor | Num, 0 | F °C |
Zone Humidity | ZoneHumidity | zone, air, humidity, sensor | Num, 0 | %RH |
Zone Humidity Setpoint | ZoneHumidSp | air, zone, sp, humidity | Num, 0 | %RH |
Occupied Cooling Setpoint | OccCoolSp | occ, cooling, zone, air, temp, sp | Num, 0 | F °C |
Occupied Heating Setpoint | OccHeatSp | occ, heating, zone, air, temp, sp | Num, 0 | F °C |
Unoccupied Cooling Setpoint | UnoccCoolSp | unocc, cooling, zone, air, temp, sp | Num, 0 | F °C |
Unoccupied Heating Setpoint | UnoccHeatSp | unocc, heating, zone, air, temp, sp | Num, 0 | F °C |
Discharge Air Points - VAV Zones |
|
|
|
|
DA Fan Command (single or common) | DaFanCmd | discharge, air, fan, run, cmd | Bool | On/Off |
DA Fan Status (single or common) | DaFanSts | discharge, air, fan, run, sensor | Bool | On/Off |
DA Fan Speed (single or common) | DaFanSpd | discharge, air, fan, speed, cmd | Num, 0 | % |
DA Fan Frequency (single or common) | DaFanFreq | discharge, air, fan, freq, sensor | Num, 0 | Hz |
DA Humidity | DaHumidity | discharge, air, humidity, sensor | Num, 0 | % |
DA Pressure | DaPress | discharge, air, pressure, sensor | Num, .01 | in w.c Pa. |
DA Pressure Setpoint | DaPressSp | discharge, air, pressure, sp | Num, .01 | in w.c. Pa |
DA Temp | DaTemp | discharge, air, temp, sensor | Num, 1 | F °C |
DA Temp Setpoint | DaTempSp | discharge, air, temp, sp | Num, 0 | F °C |
Systems with Return Air |
|
|
|
|
RA CO2 | RaCO2 | return, co2, sensor | Num, 0 | ppm |
RA CO2 Setpoint | RaCO2Sp | return, co2, sp | Num, 0 | ppm |
RA Damper Position | RaDmprPos | return, air, damper, cmd | Num, 0 | % |
RA DeHumidify Setpoint | RaDehumidSp | return, air, humidity, deHumidify, sp | Num, 0 | %RH |
RA Humidify Setpoint | RaHumidSp | return, air, humidity, humidify, sp | Num, 0 | %RH |
RA Humidity | RaHumidity | return, air, humidity, sensor | Num, 0 | %RH |
RA Fan Command (single or common) | RaFanCmd | return, air, fan, run, cmd | Bool | On/Off |
RA Fan Status (single or common) | RaFanSts | return, air, fan, run, sensor | Bool | On/Off |
RA Fan Speed (single or common) | RaFanSpd | return, air, fan, speed, cmd | Num, 0 | % |
RA Fan Frequency (single or common) | RaFanFreq | return, air, fan, freq, sensor | Num, 0 | Hz |
RA Pressure | RaPress | return, air, pressure, sensor | Num, .01 | in w.c. Pa |
RA Pressure Setpoint | RaPressSp | return, air, pressure, sp | Num, .01 | in w.c. Pa |
RA Temp | RaTemp | return, air, temp, sensor | Num, 1 | F °C |
Systems with Relief Air |
|
|
|
|
Relief Air Damper Position | RlfDmprPos | relief, air, damper, cmd | Num, 0 | % |
Systems with Outside Air |
|
|
|
|
Outside Air Damper Command (open/closed) | OaDmprCmd | outside, air, damper, cmd | Bool | Open/Closed |
Outside Air Damper Position | OaDmprPos | outside, air, damper, cmd | Num, 0 | % |
Outside Air Flow | OaFlow | outside, air, flow, sensor | Num, 0 | Cfm m³/h |
Outside Air Humidity | OaHumidity | outside, air, humidity, sensor | Num, 0 | %RH |
Outside Air Temperature | OaTemp | outside, air, temp, sensor | Num, 1 | F °C |
Mixed Air Points |
|
|
|
|
Mixed Air Temp | MaTemp | mixed, air, temp, sensor | Num, 1 | F °C |
Mixed Air Damper Position | MaDmprPos | mixed, air, damper, cmd | Num, 0 | % |
Systems with Heating |
|
|
|
|
Hot Water Circulation Pump Command | HWCPCmd | hot, water circ, pump, run, cmd | Bool | On/Off |
Hot Water Circulation Pump Status | HWCPSts | hot, water circ, pump, run, sensor | Bool | On/Off |
Hot Water Valve Position | HWVlvPos | hot, water, valve, cmd | Num, 0 | % |
Preheat Valve Position | PreheatVlvPos | preHeat, water, valve, cmd | Num, 0 | % |
Heating Coil Air Leaving Temp | HCALTemp | heat, air, temp, leaving, sensor | Num, 1 | F °C |
PreHeat Coil Air Leaving Temp | PreHCALTemp | preHeat, air, temp, leaving, sensor | Num, 1 | F °C |
Systems with Cooling |
|
|
|
|
Chilled Water Pump Command | ChWCPCmd | chilled, water, pump, run, cmd | Bool | On/Off |
Chilled Water Pump Status | ChWCPSts | chilled, water, pump, run, sensor | Bool | On/Off |
Chilled Water Valve Position | ChWVlvPos | chilled, water, valve, cmd | Num, 0 | % |
Chiller Water Valve Status | ChWVlvSts | chilled, water, valve, run, sensor | Num, 0 | % |
Chiller Water Temp Entering | CHWEtemp | chilled, water, temp, entering, sensor | Num, 1 | F °C |
Chiller Water Temp Leaving | CHWLtemp | chilled, water, temp, leaving, sensor | Num, 1 | F °C |
Chilled Water Flow | CHWFlow | chilled, water, flow, sensor | Num, 0 | Gpm L/h |
Cooling Coil Air Leaving Temp | CCALTemp | cool, air, temp, leaving, sensor | Num, 1 | F °C |
Cooling Coil Air Leaving Humidity | CCALHumidity | cool, air, humidity, leaving, sensor | Num, 1 | F °C |
Systems that Economize |
|
|
|
|
Economize Mode | EconomizeMode | economize, run, cmd | Bool | Active/Inactive |
Systems that Humidify |
|
|
|
|
Humidifier Enable | HumidifierEnab | humidifier, enable, cmd | Bool | Enabled/Disabled |
Humidifier Command | HumidifyCMD | humidifier, run, cmd | Bool | On/Off |
Systems that Dehumidify |
|
|
|
|
DeHumidify Mode | DeHumidifyMode | deHumidify, run, cmd | Bool | Active/Inactive |
Energy Points - Heat Recovery Water |
|
|
|
|
Heat Recovery Water Temp Entering | HRUWEtemp | water, temp, entering, sensor | Num, 1 | F °C |
Heat Recovery Water Temp Leaving | HRUWLTemp | water, temp, leaving, sensor | Num, 1 | F °C |
Heat Recovery Water Volumertic Flow | HRUWFlow | water, flow, sensor | Num, 1 | gal/min L/h |
Heat Recovery Water Energy (accumulated) | HRUWEnergy | water, energy, sensor | Num, 0 | MMbtu kj |
Heat Recovery Water Power | HRUWPower | water, power, sensor | Num, 0 | MMbtu/h kj/h |
Heat Recovery Pump Command | HRUCPCmd | hru, circ, pump, run, cmd | Bool | On/Off |
Heat Recovery Air Leaving Temp | HRUALTemp | hru, air, temp, leaving, sensor | Num, 1 | F °C |
Chilled Beam - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Cooling Max Flow | CoolMaxFlow | cur,point,sp, flow, max, cooling | Num, | Cfm m³/h |
Cooling Min Flow | CoolMinFlow | cur, point, sp, cooling, min, flow | Num, | Cfm m³/h |
Discharge Air Flow | DAFlow | cur, air, discharge, sensor, point, flow | Num, | Cfm m³/h |
Discharge Air Flow Setpoint | DAFlowSp | cur, air, effective, point, discharge, flow | Num, | Cfm m³/h |
Discharge Air Temperature | DaTemp | cur, air, discharge, sensor, point, temp | Num, | °F °C |
Damper Position | DmprPos | cur, air, damper, point, cmd | Num, | % |
Occupied Mode | Occ | cur, point, cmd, occupied | Bool | Unoccupied/Occupied |
Occupied Cooling Setpoint | OccCoolSp | cur, air, occ, sp, cooling, point, zone, temp | Num, | °F °C |
Unoccupied Cooling Setpoint | UnoccCoolSp | cur, air, zone, temp, cooling, point, sp, unocc | Num, | °F °C |
Zone CO2 | ZoneCO2 | cur, co2, point, sensor, air, zone | Num, | ppm |
Zone CO2 Setpoint | ZoneCO2Sp | cur, co2, point, sp, air, zone | Num, | ppm |
Zone Humidity | ZoneHumidity | cur, air, zone, sensor, point, humidity | Num, | %RH |
Zone Humidity Setpoint | ZoneHumiditySp | cur, air, zone, sp, point, humidity | Num, | %RH |
Zone Temperature | ZoneTemp | point, sensor, cur, air, temp, zone | Num, | °F °C |
Zone Temperature Setpoint (effective) | ZoneTempSp | cur, air, effective, sp, point, zone, temp | Num, | °F °C |
Radiant Heat - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Hot Water Valve | HWVIvIPos | cur, hot, point, cmd, radiant, water, valve | Num, | % |
Occupied Mode | Occ | cur, radiant, occupied, point, cmd | Bool | Unoccupied/Occupied |
Occupied Heating Setpoint | OccHeatSp | cur, radiant, occ, heating, temp, point, zone, sp | Num, | °F °C |
Unoccupied Heating Setpoint | UnccHeatSp | cur, radiant, zone, sp, unocc, point, heating, temp | Num, | °F °C |
Zone Temperature | ZoneTemp | point, sensor, cur, radiant, temp, zone | Num, | °F °C |
Zone Temperature Setpoint (effective) | ZoneTempSp | cur, radiant, effective, sp, point, zone, temp | Num, | °F °C |
Unit Heater - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Fan Command | FanCmd | cur, run, fan, point, cmd | Str | off/low/medium/high |
Fan Speed | Fan Speed | cur, point, fan, speed, cmd | Bool | On/Off |
Fan Status | FanSts | cur, run, fan, point, sensor | Bool | On/Off |
Hot Water Valve | HWVIvIPos | cur, hot, water, valve, point, cmd | Num, | % |
Occupied Mode | Occ | cur, point, cmd, occupied | Bool | Unoccupied/Occupied |
Occupied Heating Setpoint | OccHeatSp | cur, air, occ, heating, temp, point, zone, sp | Num, | °F °C |
Unoccupied Heating Setpoint | UnoccHeatSp | cur, air, zone, sp, unocc, point, heating, temp | Num, | °F °C |
Zone Temperature | ZoneTemp | point, sensor, cur, air, temp, zone | Num, | °F °C |
Zone Temperature Setpoint | ZoneTempSp | cur, air, effective, sp, point, zone, temp | Num, | °F °C |
VAV - Fan Powered - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Fan Speed | FanSpeed | fan, speed, run, cmd | Num, 0 | % |
Fan High Speed | FanSpeedHigh | fan, speed, high, run, cmd | Bool | On/Off |
Fan Medium Speed | FanSpeedMed | fan, speed, med, run, cmd | Bool | On/Off |
Fan Low Speed | FanSpeedLow | fan, speed, low, run, cmd | Bool | On/Off |
VAV - Cooling - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Cooling Max Flow | CoolMaxFlow | cur, point, flow, cooling, sp, max | Num, | Cfm m³/h |
Cooling Min Flow | CoolMinFlow | cur, point, sp, cooling, min, flow | Num, | Cfm m³/h |
Discharge Air Flow | DaFlow | cur, air, discharge, sensor, point, flow | Num, | Cfm m³/h |
Discharge Air Flow Setpoint | DaFlowSp | cur, air, effective, sp, point, discharge, flow | Num, | Cfm m³/h |
Discharge Air Temperature | DaTemp | cur, air, discharge, sensor, point, temp | Num, | °F °C |
Damper Position | DmprPos | cur, air damper, point, cmd | Num, | % |
Occupied Mode | Occ | cur, point, cmd, occupied | Bool | Occupied/Unoccupied |
Occupied Cooling Setpoint | OccCoolSp | cur, air, occ, sp, point, zone, temp | Num, | °F °C |
Unoccupied Cooling Setpoint | UnoccCoolSp | cur, air, zone, temp, cooling, point, sp, unocc | Num, | °F °C |
Zone CO2 | ZoneCO2 | cur, co2, point, sensor, air, zone | Num, | ppm |
Zone CO2 Setpoint | ZoneCO2Sp | cur, co2, point, sp, air, zone | Num, | ppm |
Zone Humidity | ZoneHumidity | cur, air, zone, sensor, point, humidity | Num, | %RH |
Zone Humidity Setpoint | ZoneHumiditySp | cur, air, zone, sp, point, humidity | Num, | %RH |
Zone Temperature | ZoneTemp | point, sensor, cur, air, temp, zone | Num, | °F °C |
Zone Temperature Setpoint (effective) | ZoneTempSp | cur, air, effective, sp, point, zone, temp | Num, | °F °C |
Chiller - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Chiller Enable | ChrEnab | chiller, enable, cmd | Bool | Enabled/Disabled |
Chiller Command | ChrCmd | chiller, run, cmd | Bool | On/Off |
Chiller Status | ChrSts | chiller, run, sensor | Bool | On/Off |
Condenser Water Isolation Valve | CWVlvCmd | condenser, isolation, valve, cmd | Bool | Open/Closed |
Condenser Water Circulation Pump | CWCPCmd | condenser, circ, pump, cmd | Bool | On/Off |
Condenser Water Entering Temperature | CWETemp | condenser, water, entering, temp, sensor | Num, 1 | F °C |
Condenser Water Leaving Temperature | CWLTemp | condenser, water, leaving, temp, sensor | Num, 1 | F °C |
Chilled Water Isolation Valve | ChWVlvCmd | chilled, isolation, valve, cmd | Bool | Open/Closed |
Chilled Water Entering Temperature | ChWETemp | chilled, water, entering, temp, sensor | Num, 1 | F °C |
Chilled Water Leaving Temperature | ChWLTemp | chilled, water, leaving, temp, sensor | Num, 1 | F °C |
Chilled Water Setpoint | ChWSp | chilled, water, leaving, temp, sp, | Num, 0 | F °C |
Chilled Water Flow | ChWFlow | chilled, water, flow, sensor | Num, 0 | gal/min L/h |
Oil Temp | ChrOilTemp | oil, temp, sensor | Num, 1 | F °C |
Oil Heater Command | ChrOilHeatCmd | oil, heater, run, cmd | Bool | On/Off |
Oil Heater Status | ChrOilHeatSts | oil, heater, run, sensor | Bool | On/Off |
Load | ChrLoad | load, sensor | Num, 0 | % |
Chiller Meter - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Energy Points - Electric |
|
|
|
|
Tons | ChrTons | chilled, water, power, sensor | Num, 0 | ton |
Current | ChrCurrent | mag, current, sensor | Num, 0 | A |
Volts | ChrVolts | volt, mag, sensor | Num, 0 | V |
Energy Total (accumulated) | ChrEnergy | elec, energy, total, sensor, | Num, 0 | kWh |
Power Total | ChrPower | elec, power, total, active, sensor | Num, 0 | kW |
Power Factor Total | ChrPF | pf, total, sensor | Num, 0.01 | unitless |
Energy Points - Water |
|
|
|
|
Chilled Water Temperature Entering | ChWEtemp | water, temp, entering, sensor | Num, 1 | F °C |
Chilled Water Temperature Leaving | ChWLTemp | water, temp, leaving, sensor | Num, 1 | F °C |
Chilled Water Flow | ChWFlow | water, flow, sensor | Num, 1 | gal/min L/h |
Chilled Water Volume (accumulated) | ChWVolume | water, volume, total, sensor | Num, 0 | Gal L |
Chilled Water Energy (accumulated) | ChWEnergy | water, energy, sensor | Num, 0 | btu |
Chilled Water Power | ChWPower | water, power, sensor | Num, 0 | btu/h |
Boiler - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Boiler Enable | BlrEnab | boiler, enable, cmd | Bool | Enabled/Disabled |
Boiler Command | BlrCmd | boiller, run, cmd | Bool | On/Off |
Boiler Status | BlrSts | boiller, run, sensor | Bool | On/Off |
Entering Water Temperature | BlrETemp | entering, water, temp, sensor | Num, 1 | F °C |
Leaving Water Temperature | BlrLTemp | leaving, water, temp, sensor | Num, 1 | F °C |
Boiler Leaving Setpoint | BlrLTempSp | leaving, water, temp, sp | Num, 0 | F °C |
Boiler Isolation Valve | BlrVlvCmd | isolation, valve, cmd | Bool | Open/Closed |
Boiler Circulation Pump | BlrCPCmd | pump, circ, run, cmd | Bool | On/Off |
Burner Level | BlrLevel | boiler, level, sensor | Num, 0 | % |
Systems with Heat Recovery |
|
|
|
|
Heat Recovery Circulation Pump Command | HRUCPCmd | pump, circ, run, cmd | Bool | On/Off |
Heat Recovery Circulation Pump Status | HRUCPSts | pump, circ, run, sensor | Bool | On/Off |
Boiler Meter - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Energy Points - Gas |
|
|
|
|
Gas Flow | BlrGasFlow | gas, flow, sensor | Num, 0 | ccf/h |
Gas Volume (accumulated) | BlrGasVolume | gas, volume, sensor, | Num, 0 | ccf |
Gas Energy (accumulated) | BlrGasEnergy | gas, energy, sensor, | Num, 0 | Mmbtu kj |
Gas Power | BlrGasPower | gas, power, sensor | Num, 0 | MMbtu/h kj/h |
Energy Points - Water |
|
|
|
|
Boiler Water Temperature Entering | BlrWEtemp | water, temp, entering, sensor | Num, 1 | F °C |
Boiler Water Temperature Leaving | BlrWLTemp | water, temp, leaving, sensor | Num, 1 | F °C |
Boiler Water Flow | BlrWFlow | water, flow, sensor | Num, 1 | gal/min L/h |
Boiler Water Volume (accumulated) | BlrWVolume | water, volume, sensor | Num, 0 | Gal L |
Boiler Water Energy (accumulated) | BlrWEnergy | water, energy, sensor | Num, 0 | MMbtu kj |
Boiler Water Power | BlrWPower | water, power, sensor | Num, 0 | MMbtu/h kj/h |
Energy Points - Heat Recovery Water |
|
|
|
|
Heat Recovery Water Temp Entering | HRUWEtemp | water, temp, entering, sensor | Num, 1 | F °C |
Heat Recovery Water Temp Leaving | HRUWLTemp | water, temp, leaving, sensor | Num, 1 | F °C |
Heat Recovery Water Flow | HRUWFlow | water, flow, sensor | Num, 0 | gal/min L/h |
Heat Recovery Water Volume (accumulated) | HRUWVolume | water, volume, sensor | Num, 0 | Gal L |
Heat Recovery Water Energy (accumulated) | HRUWEnergy | water, energy, sensor | Num, 0 | MMbtu kj |
Heat Recovery Water Power | HRUWPower | water, power, sensor | Num, 0 | MMbtu/h kj/h |
Pump - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Pump Enable | PumpEnab | pump, enable, cmd | Bool | Enabled/Disabled |
Pump Command | PumpCmd | pump, run, cmd | Bool | On/Off |
Pump Status | PumpSts | pump, run, sensor | Bool | On/Off |
Pump VFD Speed | PumpVFDSpd | pump, speed, cmd | Num, 0 | % |
Pump VFD Frequency | PumpVFDFreq | pump, freq, sensor | Num, 0 | Hz |
Pump Meter - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Energy Points - Electric |
|
|
|
|
VFD Energy Total (accumulated) | VFDEnergy | pump, elec, energy, sensor | Num, 0 | kWh |
VFD Power Total | VFDPower | pump, elec, power, active, sensor | Num, 0 | kW |
Energy Points - Water |
|
|
|
|
Water Temperature Entering | Etemp | water, temp, entering, sensor | Num, 1 | F °C |
Water Temperature Leaving | LTemp | water, temp, leaving, sensor | Num, 1 | F °C |
Water Flow | Flow | water, flow, sensor | Num, 1 | gal/min L/h |
Water Volume (accumulated) | Volume | water, volume, sensor | Num, 0 | Gal L |
Water Energy (accumulated) | WtrEnergy | water, energy, sensor | Num, 0 | MMbtu kj |
Water Power | WtrPower | water, power, sensor | Num | MMBTU/h kj/h |
Electric - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Energy Points - Electric |
|
|
|
|
Energy Total (accumulated) | Energy | elec, total, energy, sensor, | Num, 0 | kWh |
Power Total | Power | elec, total, power, active, sensor | Num, 0 | kW |
Power Factor Total | PF | elec, total, pf, sensor | Num, 0.01unitless | unitless |
Power Quality Points |
|
|
|
|
Current A | Current_A | elec, phase, current, sensor | Num, 1 | A |
Current B | Current_B | elec, phase, current, sensor | Num, 1 | A |
Current C | Current_C | elec, phase, current, sensor | Num, 1 | A |
Current Average | Current_Avg | elec, avg, current, sensor | Num, 1 | A |
Volts AN | Volts_AN | elec, phase, volts, sensor | Num, 0 | V |
Volts BN | Volts_BN | elec, phase, volts, sensor | Num, 0 | V |
Volts CN | Volts_CN | elec, phase, volts, sensor | Num, 0 | V |
Volts AB | Volts_AB | elec, phase, volts, sensor | Num, 0 | V |
Volts BC | Volts_BC | elec, phase, volts, sensor | Num, 0 | V |
Volts CA | Volts_CA | elec, phase, volts, sensor | Num, 0 | V |
Power Factor A | PF_A | elec, phase, pf, sensor | Num, 0.01 | unitless |
Power Factor B | PF_B | elec, phase, pf, sensor | Num, 0.01 | unitless |
Power Factor C | PF_C | elec, phase, pf, sensor | Num, 0.01 | unitless |
Energy A (accumulated) | Energy_A | elec, phase, energy, sensor, | Num, 0 | kWh |
Energy B (accumulated) | Energy_B | elec, phase, energy, sensor, | Num, 0 | kWh |
Energy C (accumulated) | Energy_C | elec, phase, energy, sensor, | Num, 0 | kWh |
Power A | Power_A | elec, phase, power, active, sensor | Num, 0 | kW |
Power B | Power_B | elec, phase, power, active, sensor | Num, 0 | kW |
Power C | Power_C | elec, phase, power, active, sensor | Num, 0 | kW |
Apparent Power Phase A | VA_A | elec, phase, apparent, sensor | Num, 0 | kVA |
Apparent Power Phase B | VA_B | elec, phase, apparent, sensor | Num, 0 | kVA |
Apparent Power Phase C | VA_C | elec, phase, apparent, sensor | Num, 0 | kVA |
Apparent Power Sum | VA_Sum | elec, total, apparent, sensor | Num, 0 | kVA |
Reactive Power Phase A | VAR_A | elec, phase, reactive, sensor | Num, 0 | kVAR |
Reactive Power Phase B | VAR_B | elec, phase, reactive, sensor | Num, 0 | kVAR |
Reactive Power Phase C | VAR_C | elec, phase, reactive, sensor | Num, 0 | kVAR |
Reactive Power Sum | VAR_Sum | elec, total, apparent, sensor | Num, 0 | kVAR |
Volts L-N Average | Volts_LN_Avg | elec, avg, volts, sensor | Num, 0 | V |
Volts L-L Average | Volts_LL_Avg | elec, avg, volts, sensor | Num, 0 | V |
Gas - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
BlrGasFlow | GasFlow | gas, flow, sensor | Num, 0 | ft3 _gas/h m3_gas/h |
BlrGasVolume | GasVolume | gas, volume, sensor, | Num, 0 | ft3 _gas m3_gas |
BlrGasEnergy | GasEnergy | gas, energy, sensor, | Num, 0 | MMbtu kj |
BlrGasPower | GasPower | gas, power, sensor | Num, 0 | MMbtu/h kj/h |
Chilled Water System - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Chilled Water Flow | ChWFlow | chilled, flow, sensor | Num, 1 | gal/min L/h |
Chilled Water Volume (accumulated) | ChWVolume | chilled, volume, sensor, | Num, 0 | Gal L |
Chilled Water Supply Temp | ChWSTemp | chilled, water, leaving, temp, sensor | Num, 1 | F °C
|
Chilled Water Supply Temp Setpoint | ChWSTempSp | chilled, water, leaving, temp, sp | Num, 0 | F °C |
Chilled Water Return Temp | ChWRTemp | chilled, water, entering, temp, sensor | Num, 1 | F °C
|
Chilled Water Pressure Delta | ChWPressDelta | chilled, water, pressure, delta, sensor | Num, 0 | Psi kPa |
Chilled Water Pressure Delta Setpoint | ChWPressDeltaSp | chilled, water, pressure, delta, sp | Num, 0 | Psi kPa |
Chilled Water Building Loop Pumps - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Building Loop Pump Enable | ChWPEnab | chilled, water, pump, enable, cmd | Bool | Enabled/Disabled |
Building Loop Pump Command | ChWPCmd | chilled, water, pump, run, cmd | Bool | On/Off |
Building Loop Pump Status | ChWPSts | chilled, water, pump, run, sensor | Bool | On/Off |
Building Loop Pump VFD Speed | ChWPVFDSpd | chilled, water, pump, speed, cmd | Num, 0 | % |
Building Loop Pump VFD Frequency | ChWPVFDFreq | chilled, water, pump, freq, sensor | Num, 0 | Hz |
Building Loop Return Valve Command | ChWRetVlvCmd | chilled, water, return, isolation, valve, cmd | Bool | Open/Closed |
Building Loop Return Valve Sensor | ChWRetVlvSts | chilled, water, return, valve, sensor | Bool | On/Off |
Chilled Water Heat Exchanger - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Chilled Water Heat Exchanger Enabled | HxChWEnab | enable, cmd | Bool | Enabled/Disabled |
Chilled Water Heat Exchanger Command | HxChWCmd | run, cmd | Bool | On/Off |
Chilled Water Heat Exchanger Runtime | HxChWRuntime | chilled, water, total, sensor | Num, 1 | h |
Chilled Water Entering Temperature | HxChWETemp | chilled, water, entering, temp | Num, 1 | F °C |
Chilled Water Leaving Temperature | HxChWLTemp | chilled, water, leaving, temp | Num, 1 | F °C |
Chilled Water Isolation Valve | HxChWVlvCmd | chilled, water, isolation, valve, cmd | Bool | Open/Closed |
Chilled Water Circulation Pump Command | HxChWCPCmd | chilled, water, circ, pump, run, cmd | Bool | On/Off |
Chilled Water Circulation Pump Status | HxChWCPSts | chilled, water, circ, pump, run, sensor | Bool | On/Off |
Condenser Water Entering Temperature | HxCWETemp | condenser, entering, water, temp | Num, 1 | F °C |
Condenser Water Leaving Temperature | HxCWLTemp | condenser, leaving, water, temp | Num, 1 | F °C |
Condenser Water Isolation Valve | HxCWVlvCmd | condenser, isolation, valve, cmd | Bool | Open/Closed |
Condenser Circ Pump Command | HxCWCPCmd | condenser, water, circ, pump, cmd | Bool | On/Off |
Condenser Circ Pump Status | HxCWCPSts | condenser, water, circ, pump, sensor | Bool | On/Off |
CHWS Meter - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Energy Points - Water |
|
|
|
|
Chilled Water Temperature Entering | ChWEtemp | chilled, water, temp, entering, sensor | Num, 1 | F °C |
Chilled Water Temperature Leaving | ChWLTemp | chilled, water, temp, leaving, sensor | Num, 1 | F °C |
Chilled Water Flow | ChWFlow | chilled, water, flow, sensor | Num, 1 | gal/min L/h |
Chilled Water Volume (accumulated) | ChWVolume | chilled, water, volume, sensor, | Num, 0 | Gal L |
Chilled Water Energy (accumulated) | ChWEnergy | chilled, water, energy, sensor, | Num, 0 | MMbtu kj |
Chilled Water Power | ChWPower | chilled, water, power, sensor | Num, 0 | MMbtu/h kj/h |
Energy Points - Electric |
|
|
|
|
VFD Energy Total (accumulated) | ChWPVFDEnergy | chilled, water, pump, elec, energy, total, sensor, | Num, 0 | kWh |
VFD Power Total | ChWPVFDPower | chilled, water, pump, elec, power, total, active, sensor | Num, 0 | kW |
Hot Water System - Points and Associated Tags
Description | Point Name navName | Tags | Point Type | UoM |
Hot Water Flow | HWFlow | hot, water, flow, sensor | Num, 1 | gal/min L/h |
Hot Water Volume (accumulated) | HWVolume | hot, water, volume, sensor, | Num, 0 | Gal L |
Hot Water Supply Temp | HWSTemp | hot, water, leaving, temp, sensor | Num, 1 | F °C |
Hot Water Supply Temp Setpoint | HWSTempSp | hot, water, leaving, temp, sp | Num, 0 | F °C |
Hot Water Return Temp | HWRTemp | hot, water, entering, temp, sensor | Num, 1 | F °C |
Hot Water Pressure Delta | HWPressDelta | hot, water, pressure, delta, sensor | Num, 1 | psi |
Hot Water Pressure Delta Setpoint | HWPressDeltaSp | hot, water, pressure, delta, sp | Num, 1 | psi |
HWS Building Pump - Points and Associated Tags
Description | Point Name navName | Tags | Point Type | UoM |
Building Loop Pump Enable | HWPEnab | hot, water, pump, enable, cmd | Bool | Enabled/Disabled |
Building Loop Pump Command | HWPCmd | hot, water, pump, run, cmd | Bool | On/Off |
Building Loop Pump Status | HWPSts | hot, water, pump, run, sensor | Bool | On/Off |
Building Loop Pump VFD Speed | HWPVFDSpd | hot, water, pump, speed, cmd | Num, 0 | % |
Building Loop Pump VFD Frequency | HWPVFDFreq | hot, water, pump, freq, sensor | Num, 0 | Hz |
HWS Meter - Points and Associated Tags
Description | Point Name navName | Tags | Point Type | UoM |
Energy Points - Water |
|
|
|
|
Hot Water Temperature Entering | HWEtemp | hot, water, temp, entering, sensor | Num, 1 | F °C |
Hot Water Temperature Leaving | HWLTemp | hot, water, temp, leaving, sensor | Num, 1 | F °C |
Hot Water Flow | HWFlow | hot, water, flow, sensor | Num, 1 | gal/min L/h |
Hot Water Volume (accumulated) | HWVolume | hot, water, volume, sensor, | Num, 0 | Gal L |
Hot Water Energy (accumulated) | HWEnergy | hot, water, energy, sensor, | Num, 0 | MMbtu kj |
Hot Water Power | HWPower | hot, water, power, sensor | Num, 0 | MMbtu/h kj/h |
Energy Points - Electric |
|
|
|
|
VFD Energy Total (accumulated) | HWPVFDEnergy | hot, water, pump, elec, energy, total, sensor, | Num, 0 | kWh |
VFD Power Total | HWPVFDPower | hot, water, pump, elec, power, total, active, sensor | Num, 0 | kW |
Exhaust Fan - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Occupancy | Occ | occupied, cmd | Bool | Occ/UnOcc |
Exhaust Fan Enable | EFEnab | enable, cmd | Bool | Enabled/Disabled |
Exhaust Fan Command | EFCmd | fan, run, cmd | Bool | On/Off |
Exhaust Fan Status | EFSts | fan, run, sensor | Bool | On/Off |
Exhaust Damper Command | EFDmprCmd | damper, cmd | Bool | Open/Closed |
Exhaust Damper Position | EFDmprPos | damper, cmd | Num, 0 | % |
Exhaust Damper Status | EFDmprSts | damper, sensor | Bool | On/Off |
EF Meter - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
VFD Energy Total | VDFEnergy | exhaust, fan, elec, energy, total, sensor, | Num, 0 | kWh |
VFD Power Total | VFDPower | exhaust, fan, elec, power, total, active, sensor | Num, 0 | kW |
Domestic Hot Water - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Water Flow | DHWFlow | domestic, hot, water, flow, sensor | Num, 0 | gal/min L/h |
Water Volume (accumulated) | DHWVolume | domestic, hot, water, volume, sensor, | Num, 0 | Gal L |
Supply Temperature | DHWSTemp | domestic, hot, water, leaving, temp, sensor | Num, 1 | F °C |
Supply Temperature Setpoint | DHWSTempSp | domestic, hot, water, leaving, temp, sp | Num, 0 | F °C |
Return Temperature | DHWRTemp | domestic, hot, water, entering, temp, sensor | Num, 1 | F °C |
DHW Building Pumps - Points and Associated Tags
Description | Point Name navName | Tags | Point Type | UoM |
Building Loop Pump Enable | DHWPEnab | domestic, hot, water, pump, enable, cmd | Bool | Enabled/Disabled |
Building Loop Pump Command | DHWPCmd | domestic, hot, water, pump, run, cmd | Bool | On/Off |
Building Loop Pump Status | DHWPSts | domestic, hot, water, pump, run, sensor | Bool | On/Off |
Building Loop Pump VFD Speed | DHWPVFDSpd | domestic, hot, water, pump, speed, cmd | Num, 0 | % |
Building Loop Pump VFD Frequency | DHWPVFDFreq | domestic, hot, water, pump, freq, sensor | Num, 0 | Hz |
DHW Heat Exchanger - Points and Associated Tags
Description | Point Name navName | Tags | Point Type | UoM |
DHW Heat Exchanger Enabled | HxDHWEnab | domestic, enable, cmd | Bool | Enabled/Disabled |
DHW Heat Exchanger Command | HxDHWCmd | domestic, run, cmd | Bool | On/Off |
DHW Heat Exchanger Runtime | HxDHWRuntime | cur, point, total, sensor, domestic, water | Num, 1 | h |
DHW Water Entering Temperature | HxDHWETemp | domestic, entering, water, temp, sensor | Num, 1 | F °C |
DHW Water Leaving Temperature | HxDHWLTemp | domestic, leaving, water, temp, sensor | Num, 1 | F °C |
DHW Water Isolation Valve | HxDHWVlvCmd | domestic, isolation, valve, cmd | Bool | Open/Closed |
DHW Circulation Pump Command | HxDHWCPCmd | domestic, water, circ, pump, cmd | Bool | On/Off |
DHW Circulation Pump Status | HxDHWCPSts | domestic, water, circ, pump, sensor | Bool | On/Off |
HWS Water Entering Temperature | HxHWSETemp | domestic, primary, entering, water, temp, sensor | Num, 1 | F °C |
HWS Water Leaving Temperature | HxHWSLTemp | domestic, primary, leaving, water, temp, sensor | Num, 1 | F °C |
HWS Water Isolation Valve | HxHWSVlvCmd | domestic, primary, isolation, valve, cmd | Bool | Open/Closed |
HWS Circ Pump Command | HxHWSCPCmd | domestic, primary, water, circ, pump, cmd | Bool | On/Off |
HWS Circ Pump Status | HxHWSCPSts | domestic, primary, water, circ, pump, sensor | Bool | On/Off |
DHW Meter - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Energy Points - Water |
|
|
|
|
Domestic Hot Water Temperature Entering | DHWEtemp | domestic, water, temp, entering, sensor | Num, 1 | F °C |
Domestic Hot Water Temperature Leaving | DHWLTemp | domestic, water, temp, leaving, sensor | Num, 1 | F °C |
Domestic Hot Water Flow | DHWFlow | domestic, water, flow, sensor | Num, 1 | gal/min L/h |
Domestic Hot Water Volume (accumulated) | DHWVolume | domestic, water, volume, sensor, | Num, 0 | Gal L |
Domestic Hot Water Energy (accumulated) | DHWEnergy | domestic, water, energy, sensor, | Num, 0 | MMbtu kj |
Domestic Hot Water Power | DHWPower | domestic, water, power, sensor | Num, 0 | MMbtu/h kj/h |
Energy Points - Heat Recovery Water |
|
|
|
|
Heat Recovery Water Temperature Entering | HRUWEtemp | domestic, water, temp, entering, sensor | Num, 1 | F °C |
Heat Recovery Water Temperature Leaving | HRUWLTemp | domestic, water, temp, leaving, sensor | Num, 1 | F °C |
Heat Recovery Water Flow | HRUWFlow | domestic, water, flow, sensor | Num, 1 | gal/min L/h |
Heat Recovery Water Volume (accumulated) | HRUWVolume | domestic, water, volume, total, sensor | Num, 0 | Gal L |
Heat Recovery Water Energy (accumulated) | HRUWEnergy | domestic, water, energy, sensor, | Num, 0 | MMbtu kj |
Heat Recovery Water Power | HRUWPower | domestic, water, power, sensor | Num, 0 | MMbtu/h kj/h |
Cooling Tower - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Cooling Tower Enabled | CTEnab | enable, cmd | Bool | Enabled/Disabled |
Condenser Water Entering Temperature | CTCWETemp | condenser, water, entering, temp, sensor | Num, 1 | F °C |
Condenser Water Leaving Temperature | CTCWLTemp | condenser, water, leaving, temp sensor | Num, 1 | F °C |
Sump Temperature | CTSumpTemp | sump, temp, sensor | Num, 1 | F °C |
Sump Heater Command | CTSumpHtrCmd | sump, heating, run, cmd | Bool | On/Off |
Sump Heater Status | CTSumpHtrSts | sump, heating, run, sensor | Bool | On/Off |
Fan Enabled | CTFanEnab | fan, enable, cmd | Bool | Enabled/Disabled |
Fan Command | CTFanCmd | ran, run, cmd | Bool | On/Off |
Fan Status | CTFanSts | fan, run, sensor | Bool | On/Off |
Fan VFD Speed | CTFanSpd | fan, speed, cmd | Num, 0 | % |
Fan VFD Freqency | CTFanVFDFreq | fan, freq, sensor | Num, 0 | Hz |
Pump Enabled | CTCPEnab | circ, pump, enable, cmd | Bool | Enabled/Disabled |
Pump Command | CTCPCmd | circ, pump, run, cmd | Bool | On/Off |
Pump Status | CTCPSts | circ, pump, run, sensor | Bool | On/Off |
Pump VFD Speed | CTCPVFDSpd | circ, pump, speed, cmd | Num, 0 | % |
Pump VFD Frequency | CTCPVFDFreq | circ, pump, freq, sensor | Num, 0 | Hz |
Cooling Tower Meter - Points and Associated Tags
Description | Point Name | Tags | Point Type | UoM |
Energy Points – Electric FAN |
|
|
|
|
Fan VFD Energy Total (accumulated) | CTFanVFDEnergy | fan, elec, energy, total, sensor, | Num, 0 | KWh |
Fan VFD Power Total | CTFanVFDPower | fan, elec, power, total, active, sensor | Num, 0 | kW |
Energy Points – Electric Pump |
|
|
|
|
Pump VFD Energy Total (accumulated) | CTPVFDEnergy | pump, elec, energy, total, sensor, | Num, 0 | KWh |
Pump VFD Power Total | CTPVFDPower | pump, elec, power, total, active, sensor | Num, 0 | kW |